Genset Gas 
Model
Nr. Cyl/Asp.
Displ. liter
50 Hz Prime
50 Hz Stand-by
60 Hz Prime
60 Hz Stand-by
GE8291SRG85 V12-TCA  25.8  387  360 
GE8291SRG75 V12-TCA  25.8  405  380 
  Nr. Cyl/Asp.
L = In line vertical model
NA = Naturally aspirated
TC = Turbocharged
TAA = Turbocharged aftercooled
V = 90° V form model
  Displ. liter
Displacement liter
  50 Hz Prime
kVA
The prime Power is the maximum power available with varying loads for an unlimited number of hours. The average power output during a 24 h period of operation must not exceed 80% of the declared prime power between the prescribed maintenance intervals and at standard environmental conditions. A 10% overload is permissible for 1 hour every 12 hours of operation.
  50 Hz Stand-by
kVA
This is the maximum power available for a period of 500 hours/year with a mean load factor of 90% of the declared stand-by power. No kind of overload is permissible for this use.
  60 Hz Prime
kVA
The prime Power is the maximum power available with varying loads for an unlimited number of hours. The average power output during a 24 h period of operation must not exceed 80% of the declared prime power between the prescribed maintenance intervals and at standard environmental conditions. A 10% overload is permissible for 1 hour every 12 hours of operation.
  60 Hz Stand-by
kVA
This is the maximum power available for a period of 500 hours/year with a mean load factor of 90% of the declared stand-by power. No kind of overload is permissible for this use.